What SANS 1475 covers
SANS 1475-1 is the part of SANS 1475 that applies to fire extinguishers. It sets out the administrative and technical controls for the acceptable reconditioning of portable and wheeled rechargeable fire extinguishers. That scope is taken from the notice for the standard published on gov.za.
SANS 10105-1 is a separate standard. It covers the selection, installation, inspection and use of portable and wheeled fire extinguishers, and it states that reconditioning, including overall maintenance, internal inspection and pressure testing, is done in accordance with SANS 1475-1.
Clause-level requirements sit in the standards themselves, which SABS sells. Absolute Fire & Piping is SABS approved, a current member of the Industrial Fire Technology Association (IFTA) and a member of the Fire Protection Association of Southern Africa (FPASA). Several of our technicians are trained in SANS 1475, and all are registered with SAQCC Fire.
Monthly checks, annual maintenance and pressure testing
SANS 10105-1 states that a nominated responsible person should inspect extinguishers on site at least once a month, or more often where circumstances require. Fire extinguisher monthly checks cover position and type, access and visibility, location signage and operating instructions. They also cover the security seal, visible damage or corrosion, leakage or a blocked nozzle, and the pressure indicator where it's fitted. Whether the maintenance due date has passed is checked too.
That is site control, done by someone at the property. It isn't a service.
For a managing agent or body corporate, the practical job is naming a responsible person at each property and giving them the list above.
Annual maintenance is the technician's work, and it's the term we use for our extinguisher servicing. The service date and next-due date go on the equipment register.
Pressure testing is the third cycle, and it runs on a much longer interval than the other two.
How often should fire extinguishers be serviced?
We carry out annual maintenance on fire extinguishers, so each unit is serviced once a year. How often fire extinguishers should be inspected is a different matter. SANS 10105-1 puts on-site inspection at least monthly, by a nominated responsible person.
The two get mixed up easily. A property can have its monthly checks done on time and still have an extinguisher overdue for maintenance.
If a unit is faulty, damaged or condemned, we report it and quote for replacement. We leave a standby extinguisher on site.
If a monthly check turns up a problem, contact us. Site assessment queries are answered immediately and visits are scheduled within 2 or 3 working days from enquiry, access dependent. Urgent repairs are responded to immediately.
Our fire extinguisher maintenance page covers the service itself.
Pressure-testing intervals we use
Alongside annual maintenance, these are the fire extinguisher service intervals we work to for pressure testing:
- Dry chemical powder (DCP) extinguishers: every 5 years
- CO2 extinguishers: every 10 years
We test DCP units in-house. CO2 units go to IPTS. Pressure testing is a separate job from annual maintenance, so a unit can be freshly serviced and still be coming up for its test. These are our current working intervals, not a statement of what the law requires. See our fire extinguisher pressure testing page for more on the service.
What the equipment register records
For a property manager, the register is the first place to check what was serviced and when the next service falls due. Service dates and next-due dates go on it, and we send reminders before equipment is due for maintenance.
After completed work, you receive one email containing:
- Invoice
- Equipment register
- Certificate of Compliance (COC)
- Findings report
Registers are non-editable PDFs, and copies can be requested later. The documents cover only the work we did. If we service only the ground floor of a building, for example, the documents cover the ground floor and nothing else. Registers and certificates carry no extra cost.
Our Fire Equipment Registers & Certificates page has more.
Wheeled extinguishers
SANS 1475-1 covers wheeled as well as portable extinguishers, and we service wheeled units.
Keep the schedule on track
Four things to check in your own schedule:
- Someone is named to carry out the monthly check at each property.
- Every extinguisher has a readable service date and next-due date.
- Damaged or condemned units are reported and replaced.
- Pressure-testing dates are known for DCP and CO2 units.
Every job follows the same six steps:
- Enquiry
- Site assessment, where required
- Quotation
- Approval and scheduling
- Professional workmanship
- Documentation and follow-up
You approve a quotation before any work starts, and we arrange site access with you or your managing agent. We service properties across Cape Town and the Western Cape from Unit E7 Prime Park, Mocke Road, Diep River.
To book extinguisher servicing or pressure testing, call +27 21 204 7525 during business hours, WhatsApp +27 61 543 1808 or email info@afandp.co.za.
Monday to Thursday: 8am to 5pm
Friday: 8am to 3pm
For emergencies, call +27 83 256 0731.